一起變壓器風(fēng)冷系統(tǒng)電源切換故障分析及處理
劉洪晴
(廣東電網(wǎng)有限責(zé)任公司韶關(guān)供電局,廣東 韶關(guān) 512000)
摘 要:針對(duì)一起220 kV變壓器XKPLCF-8/N型風(fēng)冷系統(tǒng)電源切換回路故障,闡述了風(fēng)冷系統(tǒng)電源控制原理,及手動(dòng)與自動(dòng)控制過(guò)程,經(jīng)外部硬件回路檢查和PLC程序邏輯檢查分析,得出了該故障主要原因是PLC程序設(shè)計(jì)缺陷,對(duì)此采取有效措施,避免了變壓器跳閘事故的發(fā)生,并提出了整改建議,為現(xiàn)場(chǎng)繼保人員提供參考。
關(guān)鍵詞:變壓器;風(fēng)冷系統(tǒng);電源切換;故障分析
中圖分類號(hào):TM401+.2 文獻(xiàn)標(biāo)識(shí)碼:B 文章編號(hào):1007-3175(2020)06-0050-04
One Case of Fault Analysis and Treatment on the Power Switching of Transformer Air Cooling System
LIU Hong-qing
(Shaoguan Bureau,Guangdong Power Grid ,Shaoguan 512000, China)
Abstract: Aiming at a 220 kV transformer XKPLCF-8/N type air-cooled system power switching circuit failure, this paper describes the principle of power control of the air-cooled system, as well as the manual and automatic control processes. The external hardware loop inspection and PLC program logic inspection analysis show that the main cause of the failure is a PLC program design defect. Based on the analysis of the external hardware circuit inspection and the logic inspection of the PLC program, it was found that the main cause of the failure was a defect in the PLC program design. Effective measures were taken to avoid the occurrence of transformer tripping accidents, and rectification suggestions were proposed to provide a reference for the on-site relay personnel.
Key words: transformer; air cooling system; power switching; fault analysis
參考文獻(xiàn)
[1] 李泰霖,羅素琳.500 kV主變風(fēng)冷系統(tǒng)故障分析與處理[J]. 電氣開(kāi)關(guān),2018,56(1):94-95.
[2] 電力行業(yè)電力變壓器標(biāo)準(zhǔn)化技術(shù)委員會(huì). 電力變壓器運(yùn)行規(guī)程:DL/T 572—2010[S]. 北京:中國(guó)電力出版社,2010:1-13.
[3] 吳正偉, 李永靈, 胡桂平. 智能風(fēng)冷控制裝置在數(shù)字化變電站中的應(yīng)用研究[J]. 電氣技術(shù),2013(11):63-65.
[4] 房義明,楊俊哲,李鶴,等.220 kV主變壓器風(fēng)冷系統(tǒng)應(yīng)急電源的應(yīng)用[J]. 內(nèi)蒙古電力技術(shù),2016,34(6):74-77.