線路保護(hù)拒動(dòng)導(dǎo)致主變后備保護(hù)動(dòng)作的事故分析
程嘉誠,許超,鄧晨,趙帥,唐仁權(quán)
(國網(wǎng)江蘇省電力有限公司南京供電分公司,江蘇 南京 210019)
摘 要:介紹了一起20 kV線路保護(hù)拒動(dòng)導(dǎo)致主變后備保護(hù)動(dòng)作越級(jí)跳閘的事故,分析了事故的原因、調(diào)度及現(xiàn)場處置過程。通過對(duì)事故的復(fù)盤及計(jì)算分析,從保護(hù)配置、系統(tǒng)接線和運(yùn)行方式等方面進(jìn)一步分析了故障原因及影響范圍,并給出了在處置時(shí)減小事故影響范圍、縮短停電時(shí)間的建議,以提高配網(wǎng)供電可靠性和用戶滿意度。
關(guān)鍵詞:線路保護(hù);后備保護(hù);零序保護(hù);保護(hù)接線
中圖分類號(hào):TM773 文獻(xiàn)標(biāo)識(shí)碼:B 文章編號(hào):1007-3175(2021)03-0045-07
Analysis of Accidents Caused by Line Protection Refusal to Activate Backup Protection of Main Transformer
CHENG Jia-cheng, XU Chao, DENG Chen, ZHAO Shuai, TANG Ren-quan
(Nanjing Power Supply Company, State Grid Jiangsu Electric Power Co., Ltd, Nanjing 210019, China)
Abstract: This paper introduces an accident of a 20 kV line protection refusal causes the main transformer backup protection action to override trip. It analyzes the cause, as well as dispatching and on-site handling process of the accident. Next, by review and calculation analysis of the accident, the cause and scope of the failure were further analyzed in terms of protection configuration, system wiring and operation mode. It also gives suggestions on reducing the scope of the accident and shortening the power outage time during the disposal, so as to improve the reliability of distribution network power supply and customer satisfaction.
Key words: line protection; backup protection; zero sequence protection; protection wiring
參考文獻(xiàn)
[1] 唐衛(wèi)波.35 kV輸電線路越級(jí)跳閘事故分析及防范措施[J]. 電工技術(shù),2019(15) :100-101.
[2] 李書強(qiáng). 一起主變保護(hù)越級(jí)跳閘的分析與思考[J].魅力中國,2013(10) :295.
[3] 羅周維,李奇艷,潘平衡. 一起接地變保護(hù)越級(jí)跳閘原因分析[J]. 電工技術(shù),2020(1) :83-84.
[4] 李彥豪.20 kV配電網(wǎng)的配電設(shè)計(jì)及應(yīng)用[J]. 電力系統(tǒng)裝備,2020(11) :27-28.
[5] 湯向華,施雄杰,東志清.20 kV系統(tǒng)保護(hù)配置及整定方案[J]. 江蘇電機(jī)工程,2010,29(4) :54-55.
[6] 夏濤,熊博,秦小安.20 kV電纜及其附件選型的探討[C]//中國電力規(guī)劃設(shè)計(jì)協(xié)會(huì)2016 年供用電設(shè)計(jì)技術(shù)交流會(huì)論文集,2016 :689-692.
[7] 葛維標(biāo),周靈江,馬匡萍,等.20 kV配電網(wǎng)線_纜混合線路電容電流實(shí)用計(jì)算[J]. 科技創(chuàng)新導(dǎo)報(bào),2013(22) :1.
[8] 陳福全,李鐵柱.20 kV小電阻接地系統(tǒng)零序保護(hù)整定計(jì)算探討[J]. 中國科技縱橫,2016(20) :134-135.
[9] 李中元,邱焱,李思越,等. 一起因開關(guān)拒動(dòng)故障而導(dǎo)致的變壓器事故分析[J]. 黑龍江電力,2019,41(6) :513-516.
[10] 黃志龍.20 kV配電網(wǎng)的中性點(diǎn)接地方式研究[J].現(xiàn)代科學(xué)儀器,2018(5) :102-104.
[11] 許超, 周科峰, 顧春華, 等. 出線開關(guān)拒動(dòng)致35 kV全站失電的分析[J]. 電工電氣,2020(9) :33-37.