Suzhou Electric Appliance Research Institute
期刊號(hào): CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁(yè) >> 文章檢索 >> 往年索引

10 kV開關(guān)柜梅花觸頭彈簧變形原因分析

來(lái)源:電工電氣發(fā)布時(shí)間:2022-03-24 13:24 瀏覽次數(shù):554

10 kV開關(guān)柜梅花觸頭彈簧變形原因分析

宋淼,馬飛,陸軍
(江蘇南瑞帕威爾電氣有限公司,江蘇 南京 211100)
 
    摘 要:10 kV 開關(guān)柜梅花觸頭在長(zhǎng)時(shí)間運(yùn)行后發(fā)生變形。通過(guò)對(duì)三組梅花觸頭彈簧進(jìn)行宏觀檢查、材質(zhì)成分分析、力學(xué)性能試驗(yàn)以及彈簧對(duì)觸指壓力校核,查找、確定梅花觸頭彈簧發(fā)生變形的原因。結(jié)果表明:造成梅花觸頭彈簧變形是由于彈簧安裝運(yùn)行后,出現(xiàn)了拉力值低于設(shè)計(jì)要求的下降,引起觸頭發(fā)熱和彈簧變形。通過(guò)對(duì)彈簧變形原因的分析,提出合理的解決方案,使該問(wèn)題得到有效預(yù)防。
    關(guān)鍵詞:10 kV 開關(guān)柜;觸頭彈簧;變形
    中圖分類號(hào):TM591     文獻(xiàn)標(biāo)識(shí)碼:B     文章編號(hào):1007-3175(2022)03-0056-03
 
Reason Analysis on Quincunx Contact Spring
Deformation of 10 kV Switchgear
 
SONG Miao, MA Fei, LU Jun
(Jiangsu Nari Power Electric Co., Ltd, Nanjing 211100, China)
 
    Abstract: The quincunx contact spring of 10 kV switchgear is deformed after a long-time operation.This paper examined the quincunx contact spring, analyzed the material of this kind of spring, tested the mechanics and strength of the spring, and checked the pressure of the contactor. All these movements helped to determine the spring deformation reason.The result shows that the deformation of the contact spring is caused by the decrease of the tension value lower than the design requirements after the spring is installed and operated, resulting in contact heating and spring deformation.This study provides a reasonable solution and prevents the problem before it happens.
    Key words: 10 kV switchgear; contact spring; deformation
 
參考文獻(xiàn)
[1] 孟濤,張丙江,王亞魯,等. 中置柜梅花觸頭發(fā)熱機(jī)理分析及改進(jìn)設(shè)計(jì)[J] . 山東電力技術(shù),2019,46(10) :32-35.
[2] 曹志民, 吳小釗, 劉永慶, 等. 一種非自力型梅花觸頭抱緊力計(jì)算方法[J] . 高壓電器,2015,51(8) :98-101.
[3] 黎斌.SF6 高壓電器設(shè)計(jì)[M].3 版. 北京:機(jī)械工業(yè)出版社,2010.
[4] 倪惠浩,張小虎. 一種 10 kV 小車開關(guān)梅花觸頭彈簧拆裝專用工具的研制與應(yīng)用[J] . 機(jī)電信息,2018(3) :35.
[5] 胡金祥. 彈簧觸指的設(shè)計(jì)與應(yīng)用[J] . 電工電氣,2017(10) :60-64.